40 CFR §82.156 · §82.157 · 40 CFR Part 84 Subpart C

EPA 608 Study Guide & 40 CFR Reference Tables

Verified regulatory thresholds for Core, Type I, Type II, and Type III certification—compiled directly from 40 CFR Part 82 Subpart F and 40 CFR Part 84, paired with an interactive lookup flash drill and a 2-page printable PDF reference sheet.

1. Required Evacuation Vacuum Levels (40 CFR §82.156 Table 1)

Before opening an appliance for major service/repair or final disposal, recover refrigerant to the threshold determined by appliance pressure class, charge size, and recovery equipment manufacture date (before vs. on/after November 15, 1993).

Appliance Category Equipment Before 11/15/1993 Equipment On/After 11/15/1993 Authority
Type I Small Appliances (<= 5 lbs, operating compressor) 80% OR 4 in. Hg 90% OR 4 in. Hg 40 CFR §82.156(b)
Type I Small Appliances (<= 5 lbs, non-operating compressor) 80% OR 4 in. Hg 80% OR 4 in. Hg 40 CFR §82.156(b)
Type II Very High-Pressure (> 355 psia at 104°F) 0 in. Hg (0 psig) 0 in. Hg (0 psig) 40 CFR §82.156 Table 1
Type II High-Pressure (< 200 lbs charge, e.g. R-410A, R-22) 0 in. Hg (0 psig) 0 in. Hg (0 psig) 40 CFR §82.156 Table 1
Type II High-Pressure (>= 200 lbs charge, e.g. R-410A, R-22) 4 in. Hg vacuum 10 in. Hg vacuum 40 CFR §82.156 Table 1
Type II Medium-Pressure (< 200 lbs charge, e.g. R-134a, R-12) 4 in. Hg vacuum 10 in. Hg vacuum 40 CFR §82.156 Table 1
Type II Medium-Pressure (>= 200 lbs charge, e.g. R-134a, R-12) 4 in. Hg vacuum 15 in. Hg vacuum 40 CFR §82.156 Table 1
Type III Low-Pressure (< 45 psia at 104°F, e.g. R-123, R-11) 25 mm Hg absolute 25 mm Hg absolute 40 CFR §82.156 Table 1

Non-major repair exception (40 CFR §82.156(a)(1)): If evacuation of the appliance to the atmosphere is not to be performed after service and the maintenance, service, or repair is not major (§82.152), evacuate medium-, high-, or very-high-pressure appliances to no higher than 0 psig before opening (or pressurize low-pressure appliances to no higher than 0 psig; for oil changes under §82.156(a)(1)(iii), evacuate or pressurize to no higher than 5 psig).

Leak exception (40 CFR §82.156(a)(2)): Separate from non-major repairs, if leaks make Table 1 evacuation unattainable or pulling a vacuum would substantially contaminate recovered refrigerant, isolate leaking from non-leaking components wherever possible, evacuate non-leaking parts to full Table 1 levels, and evacuate leaking components to the lowest level that can be attained without substantially contaminating the refrigerant—that level may not exceed 0 psig (0 psig is an upper ceiling, not a stop target).

2. Leak Repair Thresholds: 40 CFR §82.157 vs. AIM Act 40 CFR §84.106

Do not conflate 40 CFR §82.157 (appliances holding ≥ 50 lbs of ODS refrigerants) with 40 CFR §84.106 (AIM Act Subpart C rule covering appliances holding ≥ 15 lbs of HFCs or substitutes >53 GWP starting January 1, 2026—excluding appliances in the residential and light commercial air conditioning and heat pump subsector under 40 CFR §84.106(a)(3)(ii)).

Appliance Sector Annual Trigger Rate 40 CFR Part 82 Scope 40 CFR Part 84 Scope Required Action & Records
Industrial Process Refrigeration (IPR) 30% annualized >= 50 lbs ODS (40 CFR §82.157) >= 15 lbs HFC/sub >53 GWP (§84.106, eff. Jan 1, 2026) 30 days repair (120 days if process shutdown) (3-yr records)
Commercial Refrigeration 20% annualized >= 50 lbs ODS (40 CFR §82.157) >= 15 lbs HFC/sub >53 GWP (§84.106, eff. Jan 1, 2026) 30 days repair + initial & 10-day follow-up test (3-yr records)
Comfort Cooling (Chillers / Non-Excluded) 10% annualized >= 50 lbs ODS (40 CFR §82.157) >= 15 lbs HFC/sub >53 GWP; excludes res./light-comm. AC & HP (§84.106(a)(3)(ii)) 30 days repair + initial & 10-day follow-up test (3-yr records)

3. Recovery Cylinders, DOT Rules & Core Safety

Topic Standard / Limit Regulatory Basis
Recovery Cylinder Color Gray body with a yellow top (shoulder) 40 CFR §82.158 / AHRI Guideline N
Maximum Liquid Fill 80% capacity by weight (leaves 20% vapor space for thermal expansion) 49 CFR §173.304
Hydrostatic Test Interval Every 5 years for DOT-4BA / DOT-4BW refillable tanks 49 CFR §180.209
Disposable DOT-39 Cylinders Single-use only; never refill or recover into DOT-39 49 CFR §178.65
R-410A Cylinder Rating Minimum 400 psig service pressure (DOT-4BA400 / DOT-4BW400) 40 CFR §82.158 / 49 CFR §173.304
ASHRAE 34 Classes A1 (lower toxicity, no flame) · A2L (lower flammability, e.g. R-32/R-454B) · B1 (R-123) 40 CFR Part 82 Subpart G (SNAP)
Leak-Test / Brazing Purge Gas Regulated dry nitrogen only; never oxygen or compressed shop air 40 CFR §82.154 & OSHA Safety

4. Type III Low-Pressure Chiller Service Sequence (R-11 / R-123)

  1. Protect against sub-32°F tube freezing: Keep chilled-water and condenser-water pumps circulating (or drain water boxes) whenever refrigerant pressure drops below the 32°F saturation point during recovery.
  2. Energize the oil sump heater (~130°F): Low-pressure refrigerants dissolve heavily in cold oil; warming the oil releases trapped vapor so recovery holds at 25 mm Hg absolute.
  3. Check standing pressure rise: Wait several minutes after shutting off recovery; rising vacuum pressure signals residual boiling refrigerant or an external air leak.
  4. Protect the 15 psig rupture disc during leak checks: Never exceed 10 psig with regulated dry nitrogen, or raise R-123 vapor pressure slightly above 0 psig by circulating warm water.
  5. Purge unit & vapor-first charging: Purge units pull non-condensables from the top of the condenser. After deep evacuation, charge vapor first until internal pressure exceeds the 32°F saturation threshold before adding liquid refrigerant.

Quick Regulation Lookup & Self-Check Flash Drill

Search all 55 regulation-cited questions by CFR section, keyword (for example, 82.157, Part 84, 25 mm Hg, rupture), or section—or download the standalone 2-page PDF cheat sheet.

Showing 55 of 55 regulation-cited flash items